X.X              SUPPLY AND EXHAUST AIRFLOW MEASURING DEVICES

A.       Airflow measuring devices of the Vortex Shedding type, capable of continuously monitoring the airflow volume of the duct served and electronically transmitting a signal linear to the airflow volume, shall be provided where indicated.  Airflow measuring devices shall be of the insertion type, or built into airflow control valves, as required, with the capability of measuring velocity over the full range of  400 to 7000 FPM. Devices shall consist of multiple velocity sensors, supported on insertion probe bars.

B.       Individual airflow sensors shall be of rugged construction, and shall not require special handling during installation. Sensors shall be mounted on support bars, as required to achieve an equal area traverse. Standard Materials shall be aluminum bars with aluminum and ABS sensors. Support bars over one foot in length shall be supported on both ends. Where utilized in corrosive air streams, sensors and support bars shall be manufactured of corrosion resistant CPVC and ABS. All mounting hardware required shall be furnished by the Laboratory Airflow Control System Manufacturer.

C.       Individual velocity sensors shall not be effected by dust, temperature, pressure, or humidity. The sensors shall be passive in nature, with no active parts within the air stream. The output from individual sensors shall be linear with respect to airflow velocity and shall be capable of sensing airflow in one direction only. The velocity sensors shall not require calibration.

D.       Multiple sensors shall be utilized in all ducts with areas over .3 square feet in accordance with the following recommendations:

 

        AREA                    RECTANGULAR                 CIRCULAR

        less than .3                1                                1             

        .3 to .8                      2                                2

        .8 to 3.0                    4                                4*                       

             Note *: Two support bars in a cross pattern

Where sensors are installed at the inlet of Pneumavalve airflow control valves, fewer sensors are allowable due to improvement of airflow profile by vanes in Pneumavalve.

E.            Velocity measurements from individual sensors shall be summed in the integrally connected airflow transmitter. The measurement shall be input and conditioned digitally to eliminate Analog-to-Digital conversion input error. The transmitter shall provide a scaleable output over the full range of control of the unit, via on-board adjustments. The output signal of the transmitter shall be industry standard electronic signals, selectable on-board via jumpers or switches, for 4-20ma, 1-5vdc or 2-10vdc. Power requirement for the transmitter shall be 24VAC or DC.

END